← Stock for sale
packs

3,000 brand new Leoch LRCF12-170 packs

3,000 units · 6.1 MWh · Belgium

  • TypePacks
  • ConditionNew, surplus inventory
  • Listed16 Jun 2026
  • PriceOn request
Availability
  • Total energy~6.12 MWh (3,000 × 2.04 kWh)
  • StatusAvailable inventory
  • Partial lotsMinimum quantities subject to negotiation
  • Pre-shipment inspectionThird-party inspection supported on request
Condition
  • ManufacturerLeoch Battery - manufactured in China
  • StandardsIEC 61427, BS EN 61427
  • CertificationsUL, CE
  • Mfg. quality systemISO 9001, ISO 14001, ISO 45001, TS 16949
Technical specifications
Electrical
  • ModelLRCF12-170
  • ChemistryLead-Carbon AGM (VRLA)
  • FormatFront-terminal monobloc · 6-cell, 12 V
  • Rated voltage12 V
  • Nominal capacity (C10)170.0 Ah · at 1.80 V/cell
  • Capacity (C3)128.7 Ah · at 42.9 A / 1.80 V/cell
  • Capacity (C1)103.2 Ah · at 103.2 A / 1.75 V/cell
  • Nominal energy (C10)2.04 kWh
  • Internal resistance≈4.0 mΩ
  • Cycle charge voltage13.8–14.4 V · 2.30–2.40 V/cell
  • Max charge current51.0 A · at 25°C
  • Max discharge current85.0 A · at 25°C
  • Self-discharge≤3.5% / month · at 25°C
  • Temp. coefficient−4 mV/cell/°C · −24 mV/°C (unit)
Cycle life (DoD)
  • 20% DoD~8,800 cycles
  • 30% DoD~6,400 cycles
  • 50% DoD~4,000 cycles
  • 80% DoD~1,600 cycles
Operating temperature
  • Discharge range−20°C to +55°C
  • Charge range−20°C to +40°C
  • Storage range−20°C to +50°C
  • Capacity at 0°C86% of C10 nominal · ~146 Ah
  • Capacity at 40°C106% of C10 nominal · ~180 Ah
Dimensions
  • Dimensions (L × W × H)560 × 126 × 320 mm
  • Weight62.0 kg
  • Terminal typeM8
  • Container materialABS · UL94V-0 flame retardant
About this lot

04 kWh per unit. LRC-series lead-carbon chemistry significantly extends cycle life beyond conventional VRLA - approximately 4,000 cycles at 50% DoD and up to 8,800 cycles at 20% DoD - with a ≥12-year design life per IEC 61427. The front-terminal M8 layout suits rack-mount telecom enclosures, UPS cabinets, solar and wind storage systems, and container-based stationary installations.